Dold & Soehne ND5019/035
Differential current monitor IL 5882Detection ranges from 30 mA → 10 A with a connected ND 5019 differential current transformer Programmable for automatic or manual reset after error rectification Rest current principle With advance warning Delete and test buttons Wire breakage detection Short reaction time Adjustable response delay LED displays for auxiliary voltage and contact position 2 x 1 changeover Detects insulation faults in earthed networks such as RCCBs but without interruption. For monitoring and preventive maintenance of electrical systems. Input | ---|--- Nominal voltage UN: | AC/DC 24 → 230 V 50/60 Hz Voltage range: | AC: 0.8 → 1.1 Un DC: 0.9 → 1.25 Un Adjustable detection range: | AC 0.03 A; 0.1 A; 0.3 A; 0.5 A; 0.6 A; 1 A; 2 A; 5 A, 10 A Output | 1 changeover for advance warning; 1 changeover for alarm Switching capacity: | NO contact: 3 A / AC 230 V, EN 60 947-5-1 NC contact: 2 A / DC 24 V EN 60 947-5-1 Thermal current (Ith): | 5 A Rated operatin

产品联系
Company: 深圳市捷比信实业有限公司
Phone: 0755-29796190
Address: 深圳市宝安区翻身路富源大厦1栋7楼
Email: momo@jepsun.com